Heat pump vs gas boiler — the numbers, and every grant that changes them

HeatPumpSwitch › Tools › Radiators vs underfloor heating: what it

Radiators vs underfloor heating: what it does to your flow temperature and SCOP

You almost certainly do not need underfloor heating. What you need is enough emitter surface to deliver your heat loss at a low flow temperature. This works out what your existing radiators can do, and what changes if you upsize a few of them.

The rule behind the numbers

Radiator output falls roughly with the 1.3 power of the temperature difference between water and room. Drop from 75 °C to 45 °C and you keep about half the output — so you need roughly twice the surface. The table below is that curve, referenced to output at 75 °C, which is the figure printed in radiator catalogues.

Flow tempOutput factor vs 75 °CSCOP
35 °C0.303.9
45 °C0.513.4
50 °C0.633.0
55 °C0.752.8
60 °C0.872.5
75 °C1.00—